| Previous Section | Next Section | Return to Table of Contents |
Specific Pollutant Maximum Daily Discharge
SEWER USE ORDINANCE
(INDUSTRIAL PRETREATMENT RULES AND REGULATIONS)
OF THE
CAMDEN COUNTY
MUNICIPAL UTILITIES AUTHORITY
CAMDEN, NEW JERSEY
USA
Definitions of special terms and links to documents referred to can be found in Section 1.2 Definitions . Abbreviations can be found in Section 1.3 Abbreviations.
Specific Pollutant Maximum Daily Discharge Limitations
Exceptions to Table I for Small Flow Commercial Users
|
TABLE I
SPECIFIC POLLUTANT Maximum Daily Discharge Limitations (mg/L) |
|
|---|---|
| Parameter | Maximum Daily Discharge Concentration |
| Flow | Monitor only |
| Biochemical Oxygen Demand (BOD5) | 1000 |
| Chemical Oxygen Demand (COD) | 1000 |
| Oils and Grease (O/G) | 100 |
| Total Suspended Solids (TSS) | 750 |
| Arsenic, Total (As, Total) | 1.0 |
| Beryllium, Total (Be, Total) | Monitor only |
| Cadmium, Total (Cd, Total) | 0.04 |
| Chromium Total (Cr, Total) | 2.0 |
| Color | Monitor only |
| Copper, Total (Cu, Total) | 1.0 |
| Cyanide, Total (CN, Total) | 1.0 |
| Cyanide, Amenable (CN, Amenable) | 1.0 |
| Lead, Total (Pb, Total) | 0.30 |
| Mercury, Total (Hg, Total) | 0.01 |
| Molybdenum, Total (Mo, Total) | Monitor only |
| Nickel, Total (Ni, Total) | 1.0 |
| Oxidation Reduction Potential (ORP) | -50(mv) |
| Phenol | Monitor only |
| Silver, Total (Ag, Total) | Monitor only |
| Zinc, Total (Zn, Total) | 4.0 |
| pH | 6.0 to 11.5 |
| Sulfide | 1.0 |
| Petroleum Hydrocarbons (PHC) | 30 |
| Total Dissolved Solids (TDS) | Monitor only |
| Total Toxic Organics (TTO) | 5.00 |
| Benzene, Toluene, Ethylbenzene, Xylenes (BTEX) | 1.50 (Screening Limit Only) |
|
* Exceptions to Table I for Small Flow Commercial Users Only
SPECIFIC POLLUTANT Maximum Daily Discharge Limitations (mg/L) |
|
|---|---|
| Parameter | Maximum Daily Discharge Concentration |
| Biochemical Oxygen Demand (BOD5) | 1500 |
| Chemical Oxygen Demand (COD) | 1500 |
| Oils and Grease (O/G) | 150 |
| Petroleum Hydrocarbons (PHC) | 45 |
* The remaining effluent limitations in Table I above apply to Small Flow Commercial Users.
| Previous Section | Next Section | Return to Table of Contents |